This is the Multiple Choice Questions Part 6 of the Series in Philippine Electrical Code (PEC) as one of the Electrical Engineering topic. In Preparation for the REE Board Exam make sure to expose yourself and familiarize in each and every questions compiled here taken from various sources including but not limited to past Board Exam Questions in Electrical Engineering field, Electrical Engineering Books, Journals and other Electrical Engineering References.
Continue Practice Exam Test Questions Part 6 of the Series
Choose the letter of the best answer in each questions.
⇐ MCQ in Philippine Electrical Code (PEC) Part 5 | REE Board Exam
251. In every kitchen, family room, living room, parlor, bedroom or similar rooms of area of dwelling units, receptacle outlets shall be installed so that no point along the floor line any wall space is more than ____ measured horizontally from an outlet in that space.
A. 2,000 mm
B. 1,800 mm
C. 1,900 mm
D. 2,100 mm
Answer: Option B
Solution:
252. The path to ground from circuits equipment and metal enclosures for conductors shall
A. have capacity to conduct safely any fault current
B. have sufficiently low impedance
C. be permanent and continuous
D. all of these
Answer: Option D
Solution:
253. RME Board October 1994
Where the voltage between conductors does not exceed 300 V and the roof has a slope of not less than 100 mm in 300 mm, the clearance can be reduced to
A. 500 mm
B. 800 mm
C. 1000 mm
D. 900 mm
Answer: Option C
Solution:
254. RME Board April 1995
The uses of non-metallic extensions are NOT allowed in all but one of the following. Which one is this?
A. As an aerial cable
B. Where exposed to corrosive vapors
C. Where subject to corrosive vapors
D. Through floors or partitions
Answer: Option C
Solution:
255. RME Board April 1996
What is the minimum horizontal clearance for open conductors from windows, doors, porches, fire escapes or similar location?
A. 1800 mm
B. 1500 mm
C. 1200 mm
D. 1000 mm
Answer: Option D
Solution:
256. RME Board Exam April 1995
What is the maximum allowed temperature of type TW conductors?
A. 75°C
B. 50°C
C. 60°C
D. 90°C
Answer: Option C
Solution:
257. RME Board October 1995
Concealed knob and tube wiring conductors shall be rigidly supported on knobs not more than a certain minimum distance apart. What is this distance?
A. 2,000 mm
B. 1,500 mm
C. 1,300 mm
D. 2,500 mm
Answer: Option C
Solution:
258. RME Board October 1995
In the installation of power resistors, a thermal barrier shall be required if the space between the resistors and any combustible material is less than ______ mm. What is this minimum clearance?
A. 150 mm
B. 300 mm
C. 200 mm
D. 250 mm
Answer: Option B
Solution:
259. RME Board October 1995
In estimating the loading of a branch circuit, what loading shall be used for each receptacle?
A. 160 volt-ampere
B. 120 volt-ampere
C. 180 volt-ampere
D. 150 volt-ampere
Answer: Option C
Solution:
260. RME Board October 1995
Where the conduits enter a switchboard at the bottom, a sufficient space shall be provided to permit installation of the conductors in the enclosure. The minimum spacing between the bottom of the enclosure and the non-insulated bus bar shall be ________.
A. 155 mm
B. 300 mm
C. 255 mm
D. 200 mm
Answer: Option C
Solution:
261. What is the minimum vertical, horizontal or diagonal clearance for open conductors from signs, chimneys, radio and televisions, antennas, tanks, or other non-building structure?
A. 1000 mm
B. 1500 mm
C. 1800 mm
D. 1200 mm
Answer: Option A
Solution:
262. Contact device installed at the outlet for the connection of a single attachment plug.
A. Junction box
B. Reactor
C. Rosette
D. Receptacle
Answer: Option D
Solution:
263. RME Board April 1996
With respect to the safety value of the insulation on electrical maintenance tools, it can be said properly that
A. the insulation provides very little protection
B. its value is mainly to the untrained electrical helper
C. the insulation should not be used as the only protective measure
D. it adequately insures the safety of the user
Answer: Option C
Solution:
264. For the range of 8.75 kW or more in rating, the minimum branch circuit rating shall be
A. 30 A
B. 40 A
C. 50 A
D. 60 A
Answer: Option B
Solution:
265. Service heads and goosenecks in service entrance cable shall be ____ point of attachment of the service drop to the building.
A. above the
B. below the
C. at the center of the
D. at the back of the
Answer: Option A
Solution:
266. A disruptive discharge around or over the surface of a solid or liquid insulator.
A. Flashover
B. Sparkover
C. Corona
D. Surge
Answer: Option A
Solution:
267. The minimum size of service lateral conductors using copper wires shall be _____.
A. 5.5 mm2
B. 3.5 mm2
C. 8.0 mm2
D. 2.0 mm2
Answer: Option A
Solution:
268. Plug fuses shall not be installed in circuits exceeding ____ between conductors.
A. 125 V
B. 250 V
C. 300 V
D. 150 V
Answer: Option B
Solution:
269. RME Board April 1995
A continuous electrical load is one where the maximum current is expected to continue for a minimum duration of time. What is this minimum duration of time?
A. 1 hour
B. 4 hour
C. 3 hour
D. 2 hour
Answer: Option C
Solution:
270. Direct buried conductors and cables emerging from the ground shall be protected by enclosures or raceways extending from the minimum cover distance required to a point ____ above finished grade.
A. 2,000 mm
B. 2,500 mm
C. 2,400 mm
D. 3,000 mm
Answer: Option C
Solution:
271. For installations to supply only limited loads of a single branch circuit, service entrance conductors shall NOT be smaller than ____ hard drawn copper.
A. 3.5 mm2
B. 8.0 mm2
C. 5.5 mm2
D. 14.0 mm2
Answer: Option A
Solution:
272. The upper most portion of a lightning protection system.
A. Surge Arrester
B. Lightning rod
C. Ground terminal
D. Air terminal
Answer: Option D
Solution:
273. Where no standard electrical equipment of the exact size or rating required is available, ____ maybe used.
A. the next lower standard size
B. the next larger standard size
C. any size available
D. none of these
Answer: Option B
Solution:
274. RME Board April 1995
The minimum size of service drop copper conductors allowed by the Philippine Electrical Code is one of the following. Which is the size?
A. 3.5 mm2
B. 5.5 mm2
C. 2.0 mm2
D. 8.0 mm2
Answer: Option D
Solution:
275. Entrances to rooms and other guarded locations containing exposed energized parts shall be marked with a ______.
A. welcome sign
B. no entry sign
C. warning sign
D. all of these
Answer: Option C
Solution:
276. Appliance outlets installed in a dwelling unit for specific appliances, such as laundry equipment, shall be installed within ____ of the intended location of the appliance.
A. 1,800 mm
B. 1,500 mm
C. 2,000 mm
D. 1,000 mm
Answer: Option A
Solution:
277. What is the maximum permitted load of a 20-A branch circuit?
A. 20 A
B. 15 A
C. 12 A
D. 16 A
Answer: Option D
Solution:
278. For warehouses or storage, a general lighting load of _____ shall never be used.
A. 2 VA/m2
B. 4 VA/m2
C. 8 VA/m2
D. 10 VA/m2
Answer: Option A
Solution:
279. Outlets for heavy-duty lamp holders shall be rated ______.
A. 500 VA
B. 600 VA
C. 660 VA
D. 550 VA
Answer: Option B
Solution:
280. RME Board October 1996
When fastening an outlet to a brick wall, the electrician should use no one of the following. Which one is this?
A. Expansion bolts
B. Toggle bolts
C. Temporary nail
D. Wooden plug and nail
Answer: Option A
Solution:
281. A portion of a lightning protection system extending into the earth.
A. Air terminal
B. Counterpoise
C. Surge Arrester
D. Ground terminal
Answer: Option D
Solution:
282. Open conductors passing over public streets, alleys, roads, parking areas subject to truck traffic shall maintain a vertical height _____ from finished grade.
A. 3,700 mm
B. 4,600 mm
C. 5,500 mm
D. 3,100 mm
Answer: Option C
Solution:
283. Using copper, the minimum size of service entrance conductors shall be _____.
A. 14.0 mm2
B. 8.0 mm2
C. 5.5 mm2
D. 3.5 mm2
Answer: Option B
Solution:
284. RME Board October 1996
When testing the insulation integrity of a new or old electrical wiring installation circuit of 5.5 mm2 conductors, the Code specifies a minimum insulation resistance of what value?
A. 1,000,000 ohms
B. 250,000 ohms
C. 500,00 ohms
D. 100,00 ohms
Answer: Option B
Solution:
285. What test is usually made on cables after installation?
A. Copper loss test
B. No-load test
C. Insulation resistance test
D. Ampacity test
Answer: Option C
Solution:
286. For four to six conductors in a conduit, the derating factor for the conductor ampacity is ____.
A. 70%
B. 90%
C. 80%
D. 60%
Answer: Option C
Solution:
287. RME Board October 1996
When soldering two copper surfaces together, they should be kept clean while heating by
A. applying the solder quickly
B. not admitting the open flame to touch the copper surfaces
C. frequently rubbing the tip with emery cloth
D. the use of flux
Answer: Option D
Solution:
288. Circuit of a voltage of 600 V or less in a rigid metal conduit or in a rigid metal conduit or in rigid non-metallic conduit approved for direct burial and placed under driveway and parking areas of a one or two family dwelling units, shall have minimum cover distance of ____.
A. 300 mm
B. 150 mm
C. 460 mm
D. 600 mm
Answer: Option C
Solution:
289. Plate electrodes of non ferrous metal shall be at least ____ in thickness.
A. 1.2 mm
B. 1.4 mm
C. 1.5 mm
D. 1.8 mm
Answer: Option C
Solution:
290. Conductors are selected at not less than ____ of nameplate rating of the water heater.
A. 125%
B. 100%
C. 120%
D. 130%
Answer: Option A
Solution:
291. The Philippine Electrical Code requires at no electrical installation, alteration or addition shall be connected or reconnected to any electrical power supply without _____.
A. payments of application fees
B. a certificate of inspection
C. an electrical permit
D. a certificate of completion
Answer: Option B
Solution:
292. Neutral current up to _____ is computed at 100%.
A. 100 A
B. 150 A
C. 200 A
D. 300 A
Answer: Option C
Solution:
293. RME Board October 1996
In the general layout of motors and power outlets not exceeding a total of ____ maybe including in the lighting layout provided such inclusion will not make the reading, interpretation and or checking of the said plan difficult.
A. 8
B. 10
C. 12
D. 6
Answer: Option B
Solution:
294. Direct grade level access is defined as being located not more than ____ above grade level and being readily accessible.
A. 2,000 mm
B. 1,500 mm
C. 1,800 mm
D. 2,500 mm
Answer: Option A
Solution:
295. For the armories and auditorium, the general lighting load shall be ____ VA/m².
A. 8
B. 12
C. 10
D. 16
Answer: Option A
Solution:
296. RME Board October 1999
Before the ammeter is disconnected from an energized current transformer circuit, one of the procedures should be followed. Which is the one?
A. Primary winding should be shorted
B. Secondary winding should be shorted
C. Secondary winding should be opened
D. Primary winding should be opened
Answer: Option D
Solution:
297. Power conductors on the poles, below communication conductors shall maintain a spacing distance of _____.
A. 760 mm
B. 600 mm
C. 800 mm
D. 540 mm
Answer: Option A
Solution:
298. It is the intent of the PEC that factory-installed internal wiring or the construction of the equipment need not be inspected at the time of installation of the equipment EXCEPT
A. to test for continuity
B. to test for durability
C. to detect alternator or damages
D. all of these
Answer: Option C
Solution:
299.The standard conductor sizes shall be expressed in
A. mils
B. circular mils
C. square millimeters
D. American wire gauge
Answer: Option C
Solution:
300. Mandatory rules of the PEC are characterized by the use of the word ____.
A. shall
B. should
C. both A and B
D. neither A and B
Answer: Option A
Solution:
⇒ MCQ in Philippine Electrical Code (PEC) Part 7 | REE Board Exam
Questions and Answers in Philippine Electrical Code
Following is the list of practice exam test questions in this brand new series:
P inoyBIX educates thousands of reviewers and students a day in preparation for their board examinations. Also provides professionals with materials for their lectures and practice exams. Help me go forward with the same spirit.
“Will you subscribe today via YOUTUBE?”
TIRED OF ADS?
- Become Premium Member and experienced complete ads-free content browsing.
- Full Content Access to Premium Solutions Exclusive for Premium members
- Access to PINOYBIX FREEBIES folder
- Download Reviewers and Learning Materials Free
- Download Content: You can see download/print button at the bottom of each post.
PINOYBIX FREEBIES FOR PREMIUM MEMBERSHIP:
- CIVIL ENGINEERING REVIEWER
- CIVIL SERVICE EXAM REVIEWER
- CRIMINOLOGY REVIEWER
- ELECTRONICS ENGINEERING REVIEWER (ECE/ECT)
- ELECTRICAL ENGINEERING & RME REVIEWER
- FIRE OFFICER EXAMINATION REVIEWER
- LET REVIEWER
- MASTER PLUMBER REVIEWER
- MECHANICAL ENGINEERING REVIEWER
- NAPOLCOM REVIEWER
- Additional upload reviewers and learning materials are also FREE
FOR A LIMITED TIME
If you subscribe for PREMIUM today!
You will receive an additional 1 month of Premium Membership FREE.
For Bronze Membership an additional 2 months of Premium Membership FREE.
For Silver Membership an additional 3 months of Premium Membership FREE.
For Gold Membership an additional 5 months of Premium Membership FREE.
Join the PinoyBIX community.