This is the Multiple Choice Questions Part 3 of the Series in Philippine Electrical Code (PEC) as one of the Electrical Engineering topic. In Preparation for the REE Board Exam make sure to expose yourself and familiarize in each and every questions compiled here taken from various sources including but not limited to past Board Exam Questions in Electrical Engineering field, Electrical Engineering Books, Journals and other Electrical Engineering References.
Continue Practice Exam Test Questions Part 3 of the Series
Choose the letter of the best answer in each questions.
⇐ MCQ in Philippine Electrical Code (PEC) Part 2 | REE Board Exam
101. RME Board October 1995
Metal clad cables shall be permitted for installations in the following locations EXCEPT one. Which one is this?
A. Signal circuits
B. Branch circuits
C. Direct burial in the earth
D. Aerial cable
Answer: Option C
Solution:
102. RME Board October 1996
A 15-A or a 20-A branch circuit shall be permitted to supply lighting units and other utilization devices. The rating of any one cord and plug connected appliance shall NOT exceed a certain percentage of the branch circuit rating. What is this percentage?
A. 80%
B. 90%
C. 70%
D. 60%
Answer: Option A
Solution:
103. The bonding conductor used in agricultural buildings shall be copper, insulated, covered or bare, NOT smaller than ______.
A. 8.0 mm²
B. 5.5 mm²
C. 14.0 mm2
D. 3.5 mm²
Answer: Option A
Solution:
104. In any watercraft, the motor circuit shall have an ampacity of NOT less than ____ of the motors full load current rating.
A. 125%
B. 100%
C. 115%
D. 130%
Answer: Option B
Solution:
105. RME Board October 1994
The largest size of electric metallic tubing is
A. 75 mm
B. 125 mm
C. 150 mm
D. 100 mm
Answer: Option D
Solution:
106. The overload relay used to protect each motor compressor set shall be selected to trip at NOT more than ____ of the motor-compressor rated load current.
A. 125%
B. 130%
C. 150%
D. 140%
Answer: Option D
Solution:
107. RME Board October 1994
Lamp protection shall be provided by elevation of at least ______ meters from the normal working surface.
A. 2
B. 1
C. 2.5
D. 3
Answer: Option A
Solution:
108. Type UF cables shall NOT be used ______.
A. as branch circuits
B. as service entrance
C. as direct burial to earth
D. all of these
Answer: Option B
Solution:
109. Where “U” pulls are made on the pull box, the distance between each raceway entry inside the box and the opposite wall of the box shall NOT be less than ____ times the trade diameter of the largest raceway in a row.
A. 8
B. 7
C. 6
D. 5
Answer: Option C
Solution:
110. Reference ambient temperature for explosion proof electrical equipment shall be ____ degree Celsius.
A. 30
B. 40
C. 50
D. 60
Answer: Option C
Solution:
111. Welding process wherein coalescene is produced by heating with an electric arc with or without the application of pressure and with or without the use of filler metal.
A. Resistance welding
B. Spot welding
C. Arc welding
D. All of these
Answer: Option C
Solution:
112. RME Board April 1995
The use of underground feeder cables may NOT be used in the following conditions EXCEPT one. Which one is this?
A. Embedded in concrete
B. Hazardous location
C. Direct burial
D. Theaters
Answer: Option C
Solution:
113. Face plates of insulating materials shall be noncombustible and less than ____ in thickness.
A. 2.5 mm
B. 1.5 mm
C. 2.0 mm
D. 3.0 mm
Answer: Option A
Solution:
114. Conductors supplying two or more motors shall have an ampacity equal to the sum of the FLA rating of all motors plus ____ of the highest motor FLA in the group.
A. 30%
B. 15%
C. 20%
D. 25%
Answer: Option D
Solution:
115. RME Board April 1995
Which of the following colors identifies the grounded conductor of a branch circuit?
A. Green
B. Black
C. White
D. Blue
Answer: Option C
Solution:
116. An enclosure of porcelain or other insulating materials fitting with terminals and intended for connecting the flexible chord carrying a pendant to the permanent wiring.
A. Rosette
B. Raceway
C. Cable bus
D. None of these
Answer: Option A
Solution:
117. Receptacles installed for the attachment of portable cords shall be rates at NOT lest than ____ 250 V.
A. 20 A
B. 30 A
C. 10 A
D. 15 A
Answer: Option D
Solution:
118. Motors with marked service factor of less than 1.15 shall have an overload protection equal to ____ percent of the motor’s FLA.
A. 100
B. 125
C. 120
D. 115
Answer: Option D
Solution:
119. Cables and cords supplied through plugging boxes shall be of
A. aluminum
B. copper
C. aluminum or copper
D. copper-clad aluminum
Answer: Option B
Solution:
120. RME Board October 1995
Which of the following statement is NOT correct?
A. Overcurrent devices shall be located where they will
not be exposed to physical damage.
B. Overcurrent devices shall be readily accessible.
C. Overcurrent devices maybe located inside clothes closets
D. In a multi-family dwelling, each occupant shall have ready access to all over-current device protecting his occupancy.
Answer: Option C
Solution:
121. A conductor or group of conductors, in switch-gear assemblies which serves as a common connection for two or more circuits.
A. Bus
B. Lug
C. Cut-out
D. Terminal Block
Answer: Option A
Solution:
122. The ampacity of capacitor circuit conductors shall not be less than ____ of the rated current of the capacitor.
A. 125%
B. 115%
C. 135%
D. 150%
Answer: Option C
Solution:
123. The alternate or Back-up source of power in a hospital shall have a capacity to sustain its connected loads for a minimum of ______.
A. 1.5 hours
B. 2.0 hours
C. 1.0 hours
D. 2.5 hours
Answer: Option A
Solution:
124. Cable trays shall NOT be used in ______.
A. hoistways
B. industrial establishments
C. dry locations
D. all of these
Answer: Option A
Solution:
125. The load for the required branch circuit installed for the supply of exterior signs or outline lighting shall be computed at a minimum of ____ volt-amperes.
A. 1,000
B. 1,200
C. 1,500
D. 1,600
Answer: Option B
Solution:
126. RME BOARD April 1996
The usual function of a disconnect switches in high voltage circuits is to
A. isolate from energized buses, equipment which are not in service
B. open or close the circuit under load
C. open the circuit in the event of an overload
D. maintain continuity of service
Answer: Option A
Solution:
127. Pendant conductors where not cabled and longer than a certain length shall be twisted. What length is this?
A. 1,000 mm
B. 900 mm
C. 600 mm
D. 800 mm
Answer: Option B
Solution:
128. The ampacity of the phase conductors from the generator terminals to the first over current device shall NOT be less than ____ percent of the nameplate current rating of the generator.
A. 125
B. 110
C. 115
D. 120
Answer: Option C
Solution:
129. RME Board October 1994
What is the maximum number of conductors permitted in a wireway at any cross-section, signal circuit or starter-control wires are not included?
A. 30 conductors
B. 50 conductors
C. 40 conductors
D. 25 conductors
Answer: Option A
Solution:
130. Each motor shall be provided with how many disconnects?
A. Two
B. Any number (optional requirement)
C. Only one
D. Not required by the PEC
Answer: Option C
Solution:
131. Energized parts of a generator operated at more then ______ volts to ground shall NOT be exposed to accidental contact where accessible t0 unqualified persons.
A. 50
B. 30
C. 48
D. 60
Answer: Option A
Solution:
132. A hoisting and lowering mechanism equipped with a car or platform which moves in guides in a substantially vertical direction and which serves two or more floors of a building or structure.
A. Dumbwaiter
B. Escalator
C. Elevator
D. All of these
Answer: Option C
Solution:
133. An assembly of a flexible cord with an attachment plugs on one end and a cord connector on the other.
A. Extension cord
B. Fixture cord
C. Appliance cord
D. None of these
Answer: Option A
Solution:
134. Any box not over _____cm³ in size, intended for mounting in closed building construction shall; be affixed with anchors or clamps as to provide a rigid and secure installation.
A. 1,540
B. 1,760
C. 1,800
D. 1,640
Answer: Option D
Solution:
135. In battery rooms with alkaline batteries, the shelves shall be lined with steel sheet NOT less than _____ thick.
A. 70 mm
B. 60 mm
C. 65 mm
D. 75 mm
Answer: Option D
Solution:
136. A disruptive discharge around or over the surface of a solid or liquid insulator.
A. Sparkover
B. Corona
C. Flashover
D. Skin effect
Answer: Option C
Solution:
137. Emergency lighting of ____ lux shall be provided in exit paths from all areas of attended stations.
A. 10
B. 20
C. 30
D. 15
Answer: Option A
Solution:
138. RME Board April 1994
An overheated cord often indicates
A. defective cord
B. corroded terminals
C. corroded terminals and detective cord
D. none of these
Answer: Option C
Solution:
139. Individual arrester grounding conductors shall be no smaller than ____ copper.
A. 8.0 mm²
B. 14 mm²
C. 5.5 mm²
D. none of these
Answer: Option B
Solution:
140. A generic term for an artificial source of light.
A. Lumen
B. Lux
C. Candle
D. Lamp
Answer: Option D
Solution:
141. Cable bus shall securely supported at intervals NOT exceeding
A. 3,600 mm
B. 3,000 mm
C. 3,800 mm
D. 4,000 mm
Answer: Option A
Solution:
142. Snap switched used with open wiring on insulators shall be mounted on insulating material that separates the conductors at least ____ from the surface wired over.
A. 12 mm
B. 10 mm
C. 11 mm
D. 13 mm
Answer: Option D
Solution:
143. RME Board April 1996
The usual nameplate data on DC motors include the following EXCEPT one. Which one is this?
A. Manufacturers name
B. Rated frequency
C. Rated voltage
D. Rated speed
Answer: Option B
Solution:
144. Vertical runs of wireways shall be securely supported at intervals NOT exceeding ____.
A. 4,000 mm
B. 2,400 mm
C. 3,600 mm
D. 4,500 mm
Answer: Option D
Solution:
145. Size 0.75 mm² fixture wire has an ampacity of
A. 6 A
B. 10 A
C. 4 A
D. 8 A
Answer: Option A
Solution:
146. Type MI cable shall NOT be used ____.
A. in dry, wet or continuously moist locations
B. where exposed to destructive corrosive locations
C. for services, and feeders
D. all of these
Answer: Option B
Solution:
147. Each receptacle for DC plugging boxes shall be rated at NOT less than _____.
A. 20 A
B. 30 A
C. 15 A
D. 40 A
Answer: Option B
Solution:
148. RME Board October 1995
Insulated ground conductor of 14 mm² or smaller shall be identifies by a continuous while outers along its entire length or another color which is
A. green
B. natural gray
C. striped green
D. striped white
Answer: Option B
Solution:
149. Metal covers for boxes shall be lined firmly attached insulating material not less than ____ in thickness.
A. 0.80 mm
B. 0.50 mm
C. 0.75 mm
D. 0.64 mm
Answer: Option A
Solution:
150. Electrical non-metallic tubing shall NOT be used where the voltage is over
A. 500 V
B. 230 V
C. 300 V
D. 600 V
Answer: Option D
Solution:
⇒ MCQ in Philippine Electrical Code (PEC) Part 4 | REE Board Exam
Questions and Answers in Philippine Electrical Code
Following is the list of practice exam test questions in this brand new series:
P inoyBIX educates thousands of reviewers and students a day in preparation for their board examinations. Also provides professionals with materials for their lectures and practice exams. Help me go forward with the same spirit.
“Will you subscribe today via YOUTUBE?”
TIRED OF ADS?
- Become Premium Member and experienced complete ads-free content browsing.
- Full Content Access to Premium Solutions Exclusive for Premium members
- Access to PINOYBIX FREEBIES folder
- Download Reviewers and Learning Materials Free
- Download Content: You can see download/print button at the bottom of each post.
PINOYBIX FREEBIES FOR PREMIUM MEMBERSHIP:
- CIVIL ENGINEERING REVIEWER
- CIVIL SERVICE EXAM REVIEWER
- CRIMINOLOGY REVIEWER
- ELECTRONICS ENGINEERING REVIEWER (ECE/ECT)
- ELECTRICAL ENGINEERING & RME REVIEWER
- FIRE OFFICER EXAMINATION REVIEWER
- LET REVIEWER
- MASTER PLUMBER REVIEWER
- MECHANICAL ENGINEERING REVIEWER
- NAPOLCOM REVIEWER
- Additional upload reviewers and learning materials are also FREE
FOR A LIMITED TIME
If you subscribe for PREMIUM today!
You will receive an additional 1 month of Premium Membership FREE.
For Bronze Membership an additional 2 months of Premium Membership FREE.
For Silver Membership an additional 3 months of Premium Membership FREE.
For Gold Membership an additional 5 months of Premium Membership FREE.
Join the PinoyBIX community.


Same answer in Question 143 letter B (rated frequency) and letter C (rated Frequency)
thanks for the feedback. already modified