This is the Multiple Choice Questions Part 13 of the Series in Philippine Electrical Code (PEC) as one of the Electrical Engineering topic. In Preparation for the REE Board Exam make sure to expose yourself and familiarize in each and every questions compiled here taken from various sources including but not limited to past Board Exam Questions in Electrical Engineering field, Electrical Engineering Books, Journals and other Electrical Engineering References.
Continue Practice Exam Test Questions Part 13 of the Series
⇐ MCQ in Philippine Electrical Code (PEC) Part 12 | REE Board Exam
Choose the letter of the best answer in each questions.
601. Service equipment rated over 600 V located on mezzanine floors shall be required to be accessible by permanent ____.
A. stairways
B. ladders
C. both A and B
D. neither A and B
Answer: Option C
Solution:
602. The load for household electric clothes dryer in dwelling is the larger of the nameplate or ____ VA.
A. 4,000
B. 5,000
C. 6,000
D. 8,000
Answer: Option B
Solution:
603. Each lighting and appliance branch circuit panel board shall be protected individually on the supply side by not mare than two main CBs or two sets of fuses having a combined rating not ____ than that of the panel board.
A. less
B. greater
C. both A and B
D. neither A and B
Answer: Option B
Solution:
604. The long time rating for x-ray equipment is based on an operating time of ____ minutes or longer.
A. five
B. eight
C. six
D. ten
Answer: Option A
Solution:
605. For circuits supplying loads consisting of motor operated utilization equipment that is fastened in place and that has a motor larger than 0.125 hp in combination with other loads, the total computed load shall be on ____ percent of the largest motor load plus the sum of the other loads.
A. 100
B. 125
C. 150
D. 130
Answer: Option B
Solution:
606. Exposed AC cable shall closely follow the ____ of the building.
A. finish
B. studs
C. both A and B
D. neither A and B
Answer: Option A
Solution:
607. A three- phase general purpose squirrel cage motor draws a full load current of 40 A. What id the maximum size of time delay fuses that may be used for short circuit protection?
A. 120 A
B. 80 A
C. 40 A
D. 100 A
Answer: Option B
Solution:
608. A 5.5 mm² TW copper has a conductor ampacity of ____.
A. 30 A
B. 40 A
C. 20 A
D. 50 A
Answer: Option A
Solution:
609. The branch circuit load for continuous duty receptacles shall be calculated at ____ VA per receptacle.
A. 150
B. 175
C. 180
D. 200
Answer: Option C
Solution:
610. Ground rod clamps shall be secured with at least ____ bolt(s) or cap screws
A. one
B. two
C. three
D. four
Answer: Option B
Solution:
611. Over current protection devices in emergency system shall _____.
A. be coordinated
B. clear in steps
C. not trip the main device
D. all of these
Answer: Option D
Solution:
612. The underground service conductors between the street main, including any risers at the pole or other structure or from transformer and the first point of connection to the service entrance of the conductors in a terminal box. The point of connection is considered to be the point of entrance of the service conductors into the building.
A. Service entry
B. Service raceway
C. Service lateral
D. Service drop
Answer: Option C
Solution:
613. Down conductors on a heavy duty smoke or vent stacks shall be protected from physical damage of NOT less than ____ above finish grade.
A. 2,000 mm
B. 2,300 mm
C. 2,500 mm
D. 2,400 mm
Answer: Option D
Solution:
614. The PEC permits ____ 90° bends in a single conduit run
A. one
B. two
C. three
D. four
Answer: Option D
Solution:
615. A warning sign shall be posted where ____ voltage is available in service equipment.
A. high
B. low
C. both A and B
D. neither A and B
Answer: Option A
Solution:
616. Circuits with a nominal voltage of 600 V or less in rigid metal or non-metallic conduit and placed under a minimum of 100 mm thick concrete exterior stab with no vehicular traffic shall have cover distance of ____.
A. 200 mm
B. 300 mm
C. 400 mm
D. 100 mm
Answer: Option D
Solution:
617. Conductors supplying a group of motor-generator arc welders are sized at ____of the third largest welder plus the percentage of the other welders.
A. 65%
B. 85%
C. 70%
D. 75%
Answer: Option B
Solution:
618. Which of the following statements on winding in commercial garages and shops is NOT correct?
A. The ground conductor shall be connected to the ground terminal of the utilization equipment
B. Receptacles, attachment plugs and similar devices shall be of the polarized type
C. Lamps and lamp holders for fixed lighting that are located above vehicles shall be installed not lower than 2,500 mm
D. Battery chargers and batteries being charged shall not be located in location classified as hazardous
Answer: Option C
Solution:
619. Conductors may travel horizontally through ____ sections of switchboards if isolated from busbars by a barrier.
A. horizontal
B. vertical
C. both A and B
D. neither A or B
Answer: Option B
Solution:
620. There shall be no more than ______ disconnects per service grouped in any location.
A. four
B. five
C. six
D. three
Answer: Option C
Solution:
621. When a circuit breaker handles are operated vertically rather than horizontally, the “up” position of the handle shall be the ___ position.
A. off
B. on
C. neutral
D. any of these
Answer: Option B
Solution:
622. RME Board October 1996
AC equipment on board watercraft shall operate satisfactorily at the following voltage limitations. Which one is correct?
A. Minus 5% to plus 10%
B. Minus 6% to plus 10%
C. Minus 10% to plus 6%
D. Minus 10% to plus 10%
Answer: Option A
Solution:
623. Emergency power panel conductors supplying a building are tapped on ____.
A. The line side of the service
B. Any subfed panel
C. Any circuit breaker main
D. Any feeder circuit
Answer: Option A
Solution:
624. Where buildings exceed three stories or 15 meters in height, overhead lines shall be arranged, where practicable, so that a clear space of at least ____ wide will be left to facilitate title raising of ladders when necessary for fire fighting.
A. 2,000 mm
B. 1,800 mm
C. 1,900 mm
D. 1,500 mm
Answer: Option C
Solution:
625. For the purpose of lighting protection, a smoke or vent stack is classified as heavy duty if the cross sectional area of the flue is greater than ____ square meter and the height is greater than 23 meters.
A. 0.50
B. 0.32
C. 0.42
D. 0.27
Answer: Option B
Solution:
626. Voltage drop shall be considered to service laterals run at _____ distance.
A. short
B. long
C. both A and B
D. neither A and B
Answer: Option B
Solution:
627. Conductors used in lightning protection system shall have no bend forming an included angle of less than ______.
A. 60°
B. 75°
C. 50°
D. 90°
Answer: Option D
Solution:
628. Control conductors used for load management can be routed with the service entrance conductors in the same _______.
A. raceway
B. cable
C. either A or B
D. neither A or B
Answer: Option C
Solution:
629. A lighting fixture shall be wired with a flexible lighting cord with a cross sectional area of NOT less than a certain minimum area. Which is this?
A. 0.75 mm2
C. 0.50 mm2
B. 2.00 mm2
D. 1.25 mm2
Answer: Option A
Solution:
630. Service conductors shall not be run in such a manner as to block _____ to buildings.
A. openings
B. driveways
C. both A and B
D. neither A and B
Answer: Option A
Solution:
631. Continuous duty loads shall be figured at ____ percent for branch circuits.
A. 100
B. 115
C. 120
D. 125
Answer: Option D
Solution:
632. Enclosures for over-current devices in damp or wet locations shall be identified for use in such locations and shall be mounted so there is at least _____ air space between the enclosure and the wall.
A. 10 mm
B. 12 mm
C. 15 mm
D. 20 mm
Answer: Option A
Solution:
633. What type letter for conductors has a trade name “moisture and heat resistant rubber”?
A. RH
B. RHW
C. XHHW
D. THW
Answer: Option B
Solution:
634. Grounding conductor installed over lightning cables for the purpose of interconnecting the system ground electrodes and providing lightning protection for the cables.
A. Anchor
B. Counterpoise
C. Elevation rod
D. Air terminal
Answer: Option B
Solution:
635. The surge arrester for services less than 1,000 volts connected by copper conductor to grounding electrode conductor or the equivalent grounding terminal shall NOT be smaller than _____.
A. 8.0 mm2
C. 3.5 mm2
B. 5.5 mm2
D. 2.0 mm2
Answer: Option D
Solution:
636. The OCPD for arc welders with transformers shall NOT exceed _____ percent of the primary full load current.
A. 200
B. 300
C. 250
D. 400
Answer: Option A
Solution:
637. On circuits of less than 1000V, the rating of the surge arrester shall be ___ the maximum continuous phase to ground power frequency voltage available at the point of application.
A. equal to or greater than
B. not less than
C. not less than 125%
D. none of these
Answer: Option A
Solution:
638. The long time rating used to select OCPDs to protect circuits to x-ray equipment shall be _____.
A. 125%
B. 150%
C. 175%
D. 100%
Answer: Option D
Solution:
639. A 3.5 mm2 TW copper conductor has an ampacity equal to ____.
A. 20 A
B. 15 A
C. 30 A
D. 12 A
Answer: Option A
Solution:
640. Which of the following statements on lighting fixtures NOT correct?
A. Outdoor lighting fixtures and associated equipment shall be permitted to be supported by trees
B. Metal fixtures and enclosures rated at 250 V and installed up in the ceiling shall be grounded.
C. Stranded conductors shall be used in wiring a fixture supporting chain and other movable flexible parts.
D. Fixtures and lighting equipment operating at over 250 V shall be grounded
Answer: Option D
Solution:
641. Conductors from the service point to the service disconnecting means are considered service____.
A. subpanels
B. conductors
C. both A and B
D. neither A and B
Answer: Option B
Solution:
642. Connection or fittings shall not connect grounding electrode conductors to equipment by means of _______.
A. solder
B. lugs
C. pressure connectors
D. clamps
Answer: Option A
Solution:
643. Each length of non-metallic conduit shall be clearly and durably marked at least every ______ as required.
A. 3,000 mm
B. 2,000 mm
C. 4,000 mm
D. 5,000 mm
Answer: Option A
Solution:
644. Doors leading into a transformer vault shall be kept locked and access allowed only to ______.
A. the owner
B. qualified person
C. general public
D. any person working in the building
Answer: Option B
Solution:
645. Resistors and reactors shall not be installed in close proximity to combustible materials such that it constitutes a fire hazard. What minimum clearance is required by the Code?
A. 250 mm
B. 300 mm
C. 400 mm
D. 100 mm
Answer: Option B
Solution:
646. The ground conductor shall be equal to the largest ____ conductor.
A. bonding
B. phase
C. ungrounded service
D. equipment
Answer: Option B
Solution:
647. Completely enclosed, ventilated transformers equipped with a 80C rise insulation may be installed in a room ____.
A. with concrete walls
B. designed as a vault
C. of fire resistant construction
D. built with tile blocks
Answer: Option C
Solution:
648. RME Board April 1996
In a switchboard there shall be an air space of at least _____ between the energized metal part and the door or the cabinet.
A. 30 mm
B. 20 mm
C. 15 mm
D. 25 mm
Answer: Option D
Solution:
649. Electrical metallic tubing shall be securely fastened in place within ____ of each outlet box, junction box, cabinet or fitting.
A. 300 mm
B. 600 mm
C. 900 mm
D. 800 mm
Answer: Option C
Solution:
650. Lead-in antenna conductors for television or radio equipment shall be securely _____ to antennas.
A. attached
B. fastened
C. both A and B
D. neither A or B
Answer: Option C
Solution:
⇒ MCQ in Philippine Electrical Code (PEC) Part 14 | REE Board Exam
Questions and Answers in Philippine Electrical Code
Following is the list of practice exam test questions in this brand new series:
P inoyBIX educates thousands of reviewers and students a day in preparation for their board examinations. Also provides professionals with materials for their lectures and practice exams. Help me go forward with the same spirit.
“Will you subscribe today via YOUTUBE?”
TIRED OF ADS?
- Become Premium Member and experienced complete ads-free content browsing.
- Full Content Access to Premium Solutions Exclusive for Premium members
- Access to PINOYBIX FREEBIES folder
- Download Reviewers and Learning Materials Free
- Download Content: You can see download/print button at the bottom of each post.
PINOYBIX FREEBIES FOR PREMIUM MEMBERSHIP:
- CIVIL ENGINEERING REVIEWER
- CIVIL SERVICE EXAM REVIEWER
- CRIMINOLOGY REVIEWER
- ELECTRONICS ENGINEERING REVIEWER (ECE/ECT)
- ELECTRICAL ENGINEERING & RME REVIEWER
- FIRE OFFICER EXAMINATION REVIEWER
- LET REVIEWER
- MASTER PLUMBER REVIEWER
- MECHANICAL ENGINEERING REVIEWER
- NAPOLCOM REVIEWER
- Additional upload reviewers and learning materials are also FREE
FOR A LIMITED TIME
If you subscribe for PREMIUM today!
You will receive an additional 1 month of Premium Membership FREE.
For Bronze Membership an additional 2 months of Premium Membership FREE.
For Silver Membership an additional 3 months of Premium Membership FREE.
For Gold Membership an additional 5 months of Premium Membership FREE.
Join the PinoyBIX community.